Mitsubishi Heavy Industries VRF systems to Modbus TCP/RTU Interface - 48 units
The previous part number for this item was MH-AC-MBS-48
Description
FEATURES
- Direct access to outdoor unitÕs communication bus.
- The interface is a Modbus slave able to manage Modbus TCP and Modbus RTU simultaneously.
- Capable of managing up to two simultaneous Modbus master connections
- Configuration through IP or RS-232 port.
- LED indicators to provide easy to check communication status and errors.
DIRECT CONNECTION TO VRF OUTDOOR UNITS
The gateway is directly connected to the outdoor units communication bus and enables the control of all the indoor units connected to the system.
SET UP BY LINKBOX
The configuration is carried out using Linkbox software. This one allows you to define your own settings for the device and offers extra functions such as a diagnostic feature.
Technical Details
Specification
Enclosure
- Industrial sheet metal.
- Size: 215mm x 167mm x 61mm.
- Weight: 2.025 Kg
Colour
- Gray metalised.
Power
- 100 to 240VAC~
- 50 to 60Hz
- 5W max.
- Power connector: C14 (male)
Fuse
- 250V
- 1.5A
- Dimensions: 20x5mm
Terminal wiring (for low-voltage signals)
- Per terminal: solid wires or stranded wires (twisted or with ferrule)
- 1 core: 0.75 ... 1.25mm2
- 2 cores: 0.75 ... 1.25mm2
- 3 cores: not permitted
Mounting
- Wall
Modbus TCP port
- 1 x Ethernet 10Base-T (RJ45).
A-B port
- 1 x Superlink terminals (Plug-in screw terminal block 2 poles ÒAÓ ÒBÓ). SELV
Modbus RTU ports
- 1 x Serial EIA232 (DB9 male DTE). SELV
- 1 x Serial EIA485 (Plug-in screw terminal block 2 poles). SELV
LED indicators
- 2 x Ethernet port link and activity (LNK, ACT).
- 4 x MHI Interface (OP, ERR, HOST, PAC)
Push buttons
- 1 x Reset Device
Selectors
- 1 x SLK selector
Console port
- EIA232. (DB9 female DCE). SELV
Configuration
- Via console port.
Firmware
- Allows upgrades via console port.
Operational temperature range
- 0¡C to +40¡C
Operational humidity range
- 5% to 95%, non condensing
Protection
- IP20 (IEC60529)
RoHS conformity
- Compliant with RoHS directive (2002/95/CE).
Norms and standards
- CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC)
- EN 61000-6-2
- EN 61000-6-3
- EN 60950-1
- EN 50491-3
Properties
Properties
| Technology | BMS |
| Brand | INTESIS |
| IP rating | IP20 |